One of the main issues arising during the rapid filling of a pipeline is the pressure transient which originates after the entrapped air has been expelled at the air release valve. Because of the difference in density between water and air, a pressure transient originates at the impact of the water column. Many authors have analyzed the problem, both from the theoretical and the experimental standpoint. Nevertheless, mainly vertical or horizontal pipelines have been analyzed, whereas in real field applications, the pipe profile is a sequence of ascending and descending pipes, with air release/vacuum valves at high points. To overcome lack of knowledge regarding this latter case, laboratory experiments were carried out to simulate the filling of an undulating pipeline, initially empty at atmospheric pressure. The pipe profile has a high point where an orifice is installed for air venting, so as to simulate the air release valve at intermediate high point of a supply pipeline. In the experiments, the diameter of the orifice and the opening degree of both upstream and downstream valves were varied, in order to analyze their effect on the pressure transient. The experiments were also carried out with a longer descending pipe, in order to assess the effects on the pressure surge of the air volume downstream of the orifice.

Hydraulic transients caused by air expulsion during rapid filling of undulating pipelines

Fontana N;MARINI, Gustavo;
2016-01-01

Abstract

One of the main issues arising during the rapid filling of a pipeline is the pressure transient which originates after the entrapped air has been expelled at the air release valve. Because of the difference in density between water and air, a pressure transient originates at the impact of the water column. Many authors have analyzed the problem, both from the theoretical and the experimental standpoint. Nevertheless, mainly vertical or horizontal pipelines have been analyzed, whereas in real field applications, the pipe profile is a sequence of ascending and descending pipes, with air release/vacuum valves at high points. To overcome lack of knowledge regarding this latter case, laboratory experiments were carried out to simulate the filling of an undulating pipeline, initially empty at atmospheric pressure. The pipe profile has a high point where an orifice is installed for air venting, so as to simulate the air release valve at intermediate high point of a supply pipeline. In the experiments, the diameter of the orifice and the opening degree of both upstream and downstream valves were varied, in order to analyze their effect on the pressure transient. The experiments were also carried out with a longer descending pipe, in order to assess the effects on the pressure surge of the air volume downstream of the orifice.
2016
Air valve,Entrapped air,Experimental data,Hydraulic transients,Pipes system
File in questo prodotto:
Non ci sono file associati a questo prodotto.

I documenti in IRIS sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.

Utilizza questo identificativo per citare o creare un link a questo documento: https://hdl.handle.net/20.500.12070/3770
Citazioni
  • ???jsp.display-item.citation.pmc??? ND
  • Scopus 42
  • ???jsp.display-item.citation.isi??? 31
social impact