Hybrid desiccant HVAC systems have shown several advantages, compared to conventional cooling anddehumidification systems. Therefore, their use is also spreading for tertiary and residential buildings,especially when the regeneration of the desiccant can be obtained by using available waste heat.In this paper, an experimental analysis is presented on the performances of a silica-gel desiccant wheel,inserted in a test facility characterized by an advanced desiccant air handling unit, coupled to an electricchiller, a natural gas-fired boiler and a small scale cogenerator. The desiccant wheel is regenerated byusing low temperature thermal energy recovered from the microcogenerator.The effects of the main thermal-hygrometric parameters (outdoor air humidity ratio and temperature,regeneration air temperature) on the desiccant wheel performances have been experimentally evaluated;in particular, the thermal-hygrometric properties of the process air exiting the rotor and the desiccantwheel effectiveness values have been obtained. Finally, fixing the regeneration temperature at its maximumavailable value (65 C), ventilation and internal latent loads that the desiccant wheel can handlehave been evaluated and compared to the required values, both for a set of cities all over the worldand as a function of the thermal-hygrometric outdoor conditions.
Desiccant wheel regenerated by thermal energy from a microcogenerator: experimental assessment of the performances
ANGRISANI G;ROSELLI C;SASSO M
2011-01-01
Abstract
Hybrid desiccant HVAC systems have shown several advantages, compared to conventional cooling anddehumidification systems. Therefore, their use is also spreading for tertiary and residential buildings,especially when the regeneration of the desiccant can be obtained by using available waste heat.In this paper, an experimental analysis is presented on the performances of a silica-gel desiccant wheel,inserted in a test facility characterized by an advanced desiccant air handling unit, coupled to an electricchiller, a natural gas-fired boiler and a small scale cogenerator. The desiccant wheel is regenerated byusing low temperature thermal energy recovered from the microcogenerator.The effects of the main thermal-hygrometric parameters (outdoor air humidity ratio and temperature,regeneration air temperature) on the desiccant wheel performances have been experimentally evaluated;in particular, the thermal-hygrometric properties of the process air exiting the rotor and the desiccantwheel effectiveness values have been obtained. Finally, fixing the regeneration temperature at its maximumavailable value (65 C), ventilation and internal latent loads that the desiccant wheel can handlehave been evaluated and compared to the required values, both for a set of cities all over the worldand as a function of the thermal-hygrometric outdoor conditions.File | Dimensione | Formato | |
---|---|---|---|
153_Angrisani_Desiccant_Applied Energy_2011.pdf
non disponibili
Licenza:
Non specificato
Dimensione
1.16 MB
Formato
Adobe PDF
|
1.16 MB | Adobe PDF | Visualizza/Apri Richiedi una copia |
I documenti in IRIS sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.