The mean heat transfer coefficients of R22 and R407C in the coaxial counterflow evaporator (20 mm ID) of a refrigerating vapour compression plant have been experimentally measured. The experimental conditions under which heat transfer coefficients were determined reflect a typical working situation for small-scale refrigeration systems. The heat flux ranged from 1.9 to 9.1 kW/m2 and the mass flux was varied from 30 to 140 kg/m2 s. The results illustrate that the R22 heat transfer coefficient is always greater than that of R407C. Furthermore, a comparison carried out between the experimental data and those predicted by means of the most credited literature relationships showed a strongly overprediction for R407C coefficients
Experimental evaluation of R22 and R407C Evaporative Heat Transfer Coefficients in a Vapour Compression Plant
DE ROSSI F;
2000-01-01
Abstract
The mean heat transfer coefficients of R22 and R407C in the coaxial counterflow evaporator (20 mm ID) of a refrigerating vapour compression plant have been experimentally measured. The experimental conditions under which heat transfer coefficients were determined reflect a typical working situation for small-scale refrigeration systems. The heat flux ranged from 1.9 to 9.1 kW/m2 and the mass flux was varied from 30 to 140 kg/m2 s. The results illustrate that the R22 heat transfer coefficient is always greater than that of R407C. Furthermore, a comparison carried out between the experimental data and those predicted by means of the most credited literature relationships showed a strongly overprediction for R407C coefficientsFile | Dimensione | Formato | |
---|---|---|---|
ijr_23(2000).pdf
non disponibili
Licenza:
Non specificato
Dimensione
436.54 kB
Formato
Adobe PDF
|
436.54 kB | Adobe PDF | Visualizza/Apri Richiedi una copia |
I documenti in IRIS sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.